Application:
The cables are suitable for power and lighting circuits and building wiring suitable for use in semi flush exposed conduits, embedded conduits and in closed installation ducts
Standard:
BS EN 50525-2-31. SABS 1507-2, SS 358 Part-3.
Technical Data:
Voltage Rating : Uₒ/ U – 450 / 750V
Harmonised Designation : 1.5 mm² to 630 mm² stranded class 2 – H07V-R
Temperature Range : -15°C to 70°C
Minimum Bending Radius :
Upto 10 mm² : 3 X Overall Diameter.
16 & 25 mm²: 4 X Overall Diameter
Above 25 mm² : 5 X Overall Diameter.
Cable Construction:
Conductor : Plain annealed copper conductor 1.5 mm² to 630 mm² stranded class 2 complying with BS EN 60228, HD 383, IEC 60228
Insulation : PVC (Polyvinyl Chloride ) compound type TI 1 complying with EN 50363-3, HD 21.1, IEC 60227-1, SABS 1411-2