Application:
High temperature, flame retardant cable designed for use in switch control, relay and instrumentation panels of power switchgear and for purposes such as internal connectors in rectifier equipment, motor starters and controllers
Standard:
BS6231 Type CK.
Technical Data:
Voltage Rating : 600 / 1000V
Harmonised Designation :90°C (105°C for 15,000 hours
Minimum Bending Radius :
Cable diameter ≤ 8 mm : 4 x outer diameter
Approx. diameter > 8 to 12 mm: 5 x outer diameter
Approx. diameter > 12 mm: 6 x outer diameter
Test Voltage : 4000V
Cable Construction:
Conductor :Conductor Class 5 flexible plain/metal coated stranded according to EN 60228 cl. 5
Insulation : PVC (Polyvinyl Chloride) TI3 to BS EN 50363-3
Properties:
PVC self-extinguishing and flame retardant according to EN 60332-1-2